Picture Name
  • 8100 Emergency Relief Vent
8100 Emergency Relief Vent
+

Share

  • Product Details
  • Operating Principle:

    In emergency situations, such as a fire surrounding the tank, if the pressure/vacuum valve or standard vent cannot handle the overpressure, the valve disc will open at the pre-set opening pressure, allowing the tank to rapidly vent excess pressure. Once the pressure is released, the hinged cover will return to its closed position, ensuring proper reset.

    Applications:

    • Large oil depot storage and transportation centers
    • Chemical plant liquid raw material storage areas
    • Large gas storage facilities
    • Port terminal storage and transportation systems

    Construction Materials:

    Components

    Materials

    Other Materials

    Housing

    Carbon steel(powder coating)

    304 stainless steel

    316Lstainless steel

    Valve Disc

    Aluminum alloy

    304 stainless steel

    316Lstainless steel

    (customizable upon customer request)

    Valve Diaphragm

    FEPTeflon

    Nitrile rubber

    Fluorocarbon rubber

    Cover

    Aluminum

    Carbon steel

    304 stainless steel

    316Lstainless steel

    Counterweight and Spring

    Lead

    Galvanized carbon steel

    Austenitic stainless steel

    Coated steel counterweights

    Note 1: Replacement and maintenance of the valve disc, counterweight, and spring should be carried out by personnel dispatched by the manufacturer or under remote guidance from the manufacturer.

    Valve Setting Range:

    Model

    Inlet Connection Size

    mm/in.

    Pressure

    kPa(G)

    Vacuum

    kPa(G)

    Model 8110

    Counterweight-loaded

    DN400~DN600/(16"~24")

    0.6~6.9

    /

    Model 8120

    Vacuum type

    DN400~DN600/(16"~24")

    0.6~6.9

    -0.2~-1.7

    8100 Series Model 8110/8120 Emergency Relief Vent Size Chart

    Model

    Size

    Dimensions

    Connection Bolts

    Inlet Connection Size

    in.(mm)

    Total Height

    H(mm)

    Total Width

    W(mm)

    Connection Outer Diameter

    D(mm)

    Hole

    QTY

    Thread

    Type

    8110

    /

    8120

    16"

    16"(DN400)

    276/465

    670

    595

    16

    M27

    20"

    20"(DN500)

    276/465

    780

    700

    20

    M30

    24"

    24"(DN600)

    276/465

    880

    815

    20

    M33

    ※ The actual product dimensions may vary from those listed in the table above. For products with dimensions beyond those listed in the table, please contact the manufacturer for further assistance.

     

Product application field

Pharmaceuticals

Metallurgy

Food Processing

Petrochemical

Coal Energy

Environmental Protection

Chemical

Electricity

Related Products

Our advantage

Trusted Partner

The company's business also covers the third-level professional contracting of construction mechanical and electrical installation engineering, which can provide customers with one-stop service for product development and design, manufacturing, installation and construction, and after-sales guidance.

Perfect quality system

The company has established a perfect quality management system in strict accordance with domestic and foreign industry standards. China Taian Branch cooperates closely with universities and research institutes to jointly promote technological innovation.

24-hour professional service

With professional after-sales and sincere service as the criterion, 24 hours a day, all year round to provide customers with better quality and more professional service.

8100 Emergency Relief Vent

The Model 8100 emergency relief vent is widely used in protection systems for atmospheric storage tanks with a design pressure of 6.9 kPa or less (gauge pressure at the tank top). It is typically installed horizontally at the top of the tank. In the event of a fire or excessive pressure buildup in the tank, if the pressure/vacuum valve fails or is unable to meet the required venting capacity, the emergency relief vent will activate to prevent overpressure and potential damage to the tank. The opening pressure of the emergency relief vent is set between the opening pressure of the pressure/vacuum valve and the design pressure of the tank. This ensures both material conservation and the safety of the tank.

Parameter characteristics

Applicable sizes: 16" (DN400) to 24" (DN600)

Hinged valve disc design, providing sensitive operation with minimal friction

Full-opening design structure

Advanced testing platform provides reliable flow rate curves and leakage detection reports

Optional spring-loaded vacuum type

Cost-effective with low maintenance costs

Various anti-corrosion coating options available

Modular valve body components design for easy and simple maintenance

Product Query

The main products are: special bursting disc safety device, flameless relief device, explosion-proof valve, dust suppression device, flame arrester, breathing valve, emergency relief valve, etc.

Submission